Calculatrice d'ingénierie
Bleeder Resistor and Capacitor Discharge Calculator
Comment lire le diagramme. The bleeder resistor sits directly across the capacitor, so the stored charge drains through it once the supply is removed. The curve is V = V0 × e−t/RC; the dashed line is the voltage that is safe to touch, and where the curve crosses it is the discharge time.
A high voltage capacitor stays charged after the supply is removed. This calculator gives the discharge time through a bleeder resistor, the resistance required to reach a target voltage in a given time, and the stored energy that has to be dissipated while it happens.
Contributions
Résultats
- Time constant (R×C)
- -
- Temps de décharge
- -
- Énergie stockée
- -
- Initial bleeder power
- -
- R for 60 s to 60 V
- -
La formule
V(t) = V0 × e^(−t / RC). Discharge time to a target voltage is t = R × C × ln(V0 / Vt). Stored energy is E = ½ × C × V0². The initial power in the bleeder is V0² / R, and it falls as the capacitor discharges.
Ce que la calculatrice n'inclut pas
- Absorption diélectrique. A ceramic or film capacitor recovers part of its voltage after discharge. The recovered voltage can be a few percent of the original and is why some standards require a second discharge or a permanent bleeder.
- Bleeder voltage rating. The resistor must survive the full initial voltage, not the average. A 20 kV bank needs a bleeder rated for 20 kV continuously, which usually means a series string rather than one part.
- Conditions de défaut. If the bleeder opens, the stored energy stays. Two resistors in series, or a bleeder plus a shorting bar, is the usual redundancy.
Référence de sécurité
IEC 62368-1 treats a capacitor as hazardous above 60 V DC or 20 J stored energy, and requires discharge to a safe level within a defined time after the supply is removed. The exact limit depends on the equipment class and the accessible part; the numbers above let you check the design against whichever limit applies. This page is a calculation aid, not a compliance statement.
Choosing the bleeder
Bleeder duty is continuous voltage with low current, so the resistor is usually a planar or tube thick film part with a high resistance value. Where the bank voltage exceeds a single resistor, the string is split and each element is rated for its share — see the Aperçu des résistances.
Send the capacitance, voltage and target discharge time: demander un devis techniqueRéponse sous 6 heures.